• Application: Chemical process
  • Installation country: Russia Russia
  • Hitema Hydromodule Model HYD.1100L has been designed to be matched to an ISVF.680. The double pump are cabled inside the chiller and managed by its control. This allow to use a single power supply spot in the chiller electrical board. The 1100 liters tank assure a buffer to compensate the load variations while the expansion vessel absorb the exceeding pressure when there is a flow or temperature variation. The unit can be installed outdoor thanks to the closed frame.

  • Model: HYD.1100L
  • Type: double pump
  • Country: Russia
  • Application: chemical process
  • Flow Rate: 119 m3/h
  • Available Pressure: 3,15 bar
  • Process Fluid: 40% Ethylene Glycol
  • Tank Volume: 1100 Liters
  • Expansion Vessel Volume: 60dm3
  • Matched with chiller Model: ISVF.680
  • Process Outlet Temperature: 7°C